MODEL NO: FAP232N-5L
TYPE: Wall mounting type
POWER SUPPLY: 220VAC 50/60Hz
AXU.POWER SUPPLY: 24VDC Ni-Cd battery 0.25AH ( Charging current: Approx. 4.7mA)
CIRCUIT VOLTAGE: 5,24,48VDC, 24VAC
ALARM VERIFICATION TIME: Thermal detector: 10sec; Smoke detector : 60sec.
POWER CONSUMPTION: Max.approx: 14VA for monitoring
Max.approx: 31VA for alarming
MAX.NUMBER OF APPARATUS TO BE CONNECTED:
Spot type smoke detector30/zone( Max.50/panel )
Local alarm bells: 10 ( 24VDC, 10mA/bell )
Local lamps: 5 ( 30V, 2W/lamp ) 14 ( 24V, 24mA/lamp )
AMBIENT TEMPERATURE AND HUMIDITY: 0 to 400C, 20 to 85% ( RH )
LOOP RESISTANCE OF ALARM INPUT CIRCUIT: Less than 50O/loop
END - OF - LINE RESISTOR: 10KO 1/2W
MATERIALS ( ENCLOSURE ) ABS resin with non - flammability to 94V2 ( UL )
COLOR: Beige/yellow : Nearly to Munsell 2.5Y 9/1, semi-glare
WEIGHT: Approx.2.7kg